Brief IntroductionSeveral faults of this series of soft starter forthree phase induction motor, cause analysis and solutions.FaultCause of faultSolutionsOvervoltage protectionMain circuit voltage is too high1. Check whether the main circuit voltage is too high.2. Check whether the parameter Q2
Several faults of this series of soft starter for three phase induction motor, cause analysis and solutions.
Fault | Cause of fault | Solutions |
Overvoltage protection | Main circuit voltage is too high | 1. Check whether the main circuit voltage is too high. 2. Check whether the parameter Q24 of the overvoltage protection value is set correctly. |
Undervoltage protection | Main circuit voltage is too low | 1. Check whether the main circuit voltage is too low. 2. Check whether the parameter Q26 of overvoltage protection value is set correctly |
Phase voltage imbalance | Three-phase power supply voltage imbalance | 1. Check whether the main circuit voltage is three-phase unbalanced. 2. Check whether the parameter Q23 of the voltage imbalance protection value is set correctly. |
SCR abnormality | Check whether the thyristor is short-circuited. | |
Leakage blocking | Check the insulation of three-phase winding to ground. | |
Starting timeout | Starting time is too long | 1. Check whether the current limiting signal is set too small. 2. Whether the starting time limit B12 parameter is set too small. |
SCR overheat | Internal radiator overheated? Poor ventilation of the machine | 1. Check whether the fan works reliably. 2. Reduce the starting frequency. Check whether the control power supply voltage is too low. |
Motor temperature | motor temperature detecys by PTC thermal resistor inside the motor is too high | 1. Check whether the PTC circuit is closed and the input is connected. 2. Check and correct the cause of high temperature. Restart the motor after it has cooled down enough. |
Frequent starting | Starting too often | The start frequency exceeds the set minimum start interval parameter Q09.. |
Frequency fault | Frequency out of range | Check and change the power supply frequency. |
Zero sequence protection | Check that the three-phase leakage exceeds the design value | |
Tap timeout | Tapping time is too long | The starting time exceeds the set starting time limit parameter B13. |
| Item | Basic parameters |
| Load Type | 3-phase high-voltage squirrel-cage asynchronous motor, synchronous motor |
| AC voltage | 3000---10000VAC |
| Working frequency | 50HZ / 60HZ ± 2HZ |
| Phase sequence | CMV allows to work in any phase sequence (can be set by parameter) |
| Bypass Contactor | Contactor with direct starting capacity |
| Control power | AC/DC(110-220V)±15% |