    Brief IntroductionThesolid state soft starteruses yellow LEDs to indicate that a fault has occurred and shows the corresponding fault information on the LCD display. There are 19 kinds of protection functions. When the protection function of series solid state soft starter is activated,


Simo Motor Product Details

Brief Introduction

The solid state soft starter uses yellow LEDs to indicate that a fault has occurred and shows the corresponding fault information on the LCD display. There are 19 kinds of protection functions. When the protection function of series solid state soft starter is activated, it stops immediately and the LCD display shows the current fault. Users can analyze the fault according to the fault content.

Fault

Cause of fault

Solutions

Main power supply phase loss

Lack of phase sequence at startup or during operation

Check whether the three-phase power supply is reliable phase?

Phase sequence error

Phase sequence reversed

1. Adjust the phase sequence of the three-phase main power supply.

2. Set B09 parameter to not detect phase sequence.

Parameter loss

Setting parameters missing?

Check each function item setting and reset

Overload protection

After a certain time, the current is still too high, resulting in motor overload.

1. Check and correct the cause of overload and check if the current limit multiplier is set too low.

Check whether the starting time is set too long.

3,Check whether the motor overload protection level is set reasonably.

4. Check whether the motor rated current is set correctly.

Running overcurrent

Load suddenly increased?

Load fluctuates too much?

1. Adjust the load running condition

2. Check whether the B03 parameter item is set too small.

Underload protection

Motor running current lower than rated current

1. Check the cause of underload and make corrections

2. Check whether the setting is according to the operating conditions.

Phase current imbalance

Three-phase current imbalance

1. Check if the three-phase current imbalance exceeds the imbalance protection level set in parameter item B01.

2. Adjust the load operating conditions.

Main Technical Parameters

ItemBasic parameters
Load Type

3-phase high-voltage squirrel-cage asynchronous motor

synchronous motor

AC voltage3000---10000VAC
Working frequency50HZ / 60HZ ± 2HZ
Phase sequenceCMV allows to work in any phase sequence (can be set by parameter)
Bypass ContactorContactor with direct starting capacity
Control powerAC/DC(110-220V)±15%
Transient overvoltage protectiondv/dt absorption network
Start frequency1-3 times/hour
Environmental conditions

Ambient temperature: -20-+50℃;

Relative humidity: 5%--95% non-condensing;

Altitude less than 1500 meters (more than 1500 meters need to be de-rated)

Specifications

 technical data of solid state soft starter